HVAC System Care & Duct Cleaning

This page is visible only to those with a certified link

33 XXX Circle

North Easton, MA

Project Date: 11/12/21
Contact: Sxxxx
Technician Reporting: John Cox ASCS, VSMR

Table of Contents:

 

Overview

The HVAC system and network of air ducts were visually inspected and cleaned. The work area consisted of entire living space of the first and second floors, including basement and attic. Two air handlers, one in the basement and one in the attic, were cleaned (see specifications below). There were a total 17 registers, including returns. three bathrooms with associated vents and ducting were inspected and cleaned. 425 feet of flex duct including the galvanized main trunks were inspected and cleaned. Multiple access points were used to allow for inspection and manual cleaning and also to attach a negative air machine. Two outside condenser units were also Inspected.

 

It is recommended that filters with a Merv rating of 7 or higher be changed every 90 days or as needed. Both systems were well sealed. No sign of leaks in air handlers or conduits. AHU coils and fins were intact and cleared of moderate debris.

 
 

Project & System Specifications

Cleaning Method and Air Handler componets specified on page 6 of procedural report below.

Photo Slide-Deck Click for Full View

press to zoom

press to zoom

press to zoom

press to zoom
1/10

press to zoom

press to zoom

press to zoom

press to zoom
1/12

Air Handler(s)

ahu check list.png

Two forced hot air furnaces were inspected, cataloged and cleaned. The systems were in good working order. No biological growth to be reported inside the systems. The units had humidity and moisture levels well within accepted tolerances. See photo slide-deck.

 

Ductwork, Registers & Vents

Photo Slide-Deck Click for Full View

Fans, Vents & Registers: Seventeen (17) vents and registers were removed in order to accessed ductwork for manual cleaning. Registers were summarily cleaned and replaced in a pre-recorded order.

Main Trunks: Supply trunks were found to be sealed and was cleared of a moderate amount of construction debris .Both were free of both moisture and biological contaminants. Access point were cut and re-sealed by SMACNA international standards. See photo deck.

Ductwork:  Flex duct connections were found intact. The home space was left sealed and intact. Ductwork contained a moderate amount of construction debris and was cleared. Access points were used in the ductwork to attach a Nikro 5,000 CFM HEPA negative air machine. Interior of ductwork was cleaned using mechanically rotating brushes and a 20' flexible cable with a 8" nylon brush (whip).

 

press to zoom

press to zoom

press to zoom

press to zoom
1/78
 

Containment, Equipment & Condensers

Containment Floors were protected where neccessary and .3 mil plastice was used to contain areas from possible cross-contamination.

 

Equipment: Nikro 5000 CFM Negative Air Machine. 2-Stage HEPA Filtration with 99.97% filtration. 5" static pressure, 115v/13 each of two motors. Varying sizes of Nylon and Silica rotating brushes (whips). 115v electric oil-free air compressor with forward & reverse blowing nozzles.

Condenser units: 

Two condenser units were inspected and appeared relatively new and in good working order.

press to zoom

press to zoom

press to zoom

press to zoom
1/14
 
 
inspec schedule.png